FAQ#111 - Why I cannot read correctly my 4-20mA current loop gauge?

It could be a problem connected to the power supply given by the readout or logger. When the power supply is in the current loop (2-wire gauge) it is necessary to consider the effect of voltage drop across the shunt resistor on the voltage applied to the gauge.

For example, suppose a 4-20mA gauge requires at least 12 V to operate correctly and the readout powered with 16 V. The voltage the gauge sees is the voltage supplied by the readout minus the voltage drop in the rest of the current loop. At 20 mA output, the voltage drop across the commonly used 100 ohm resistor is 2 V.

When the voltage supplied by the readout is 16 V, this leaves 14 V for the gauge and everything is fine.
However, if the readout is powered with less than 14 V, at 20 mA current it will leave less than 12 V for the gauge. In this case, the output of the transmitter may be in error.

Déformètres à fil
Inclinomètres fixes MEMS (classique)
Fissuromètres à fil
Système de tassement multipoint
MPBX - Extensomètres en forage multipoint
Extensomètre multipoint miniaturisé MEXID
Extensomètres fixes
Cellules de charge électriques pour ancrages
Cellules de pression totale
Cellules de charge électro-hydrauliques pour soutènement
Fissuromètres et jointmètres
Enregistreur de données Mini OMNIAlog
Vérins Plats – Accessoires d’essai
Cellules de charge pleines pour essais sur pieux
H-Level - Systeme tassometre hydraulique
Cannes de convergence (DISCONTINUED)
Piézomètres piézo-résistifs
Capteurs de pression relatifs
Capteur de pression amovible
Piézomètres en titane
Piézomètres à pénétration directe
Clinomètres MEMS-analogiques

 
FAQ#110 - What's the purpose of the linear and polynomial factors written in the Calibration Reports?

Utilize the Linear Sensitivity Factors (A, B) and Ploynomial Sensitivity Factors (A, B, C, D) of the Calibration Reports permit to obtain readings in engineerig units with a maximum error as for the Calibration Report.

In the case of analogue gauges, the factors shall be applied on the electrical readings (i.e. mA, mV, digit, etc...)

In the case of digital gauges in "Legacy mode" (digital gauges with FW version 0.X, 1.X, 2.X or 3.X), the factors shall be applied on the output in engineering units (i.e. sin angle, kPa, etc...)

In the case of digital gauges in "Normal Mode" (digital gauges with FW version 3 or higher), the factors are already applied inside the gauge, so the Sensitivity Factors shall not be utilized with these instruments.
NOTE: all the new digital gauges are in "Normal mode".

For more information regarding SISGEO Calibration Report, refer to the following video https://youtu.be/BF8e3ZRcaYU

For more information on "how to use" the Sensitivity Factors with analogue gauges and with digital gauges in Legacy Mode, refer to the instruments manuals or to the following document: https://www.sisgeo.com/uploads/manuali/Addendum_data_processing/ADDENDUM_-_DATA_PROCESSING_-_EN_00.pdf

 

 

LT-Inclibus
MD-Profile system

 
FAQ#091 - How can I read data from 0MEPR106000 barometer in engineering units?

The Barometer model 0MEPR106000 have a 4-20mA current loop output.
The measuring range is from 800 mbar (equivalent to 4 mA) to 1200 mbar (equivalent to 20 mA).

Manual readings are taken connecting the wires to a readout according to the following instructions:

Signal: 4-20mA current loop

Red: + Loop
Black: - Loop


The following formula allows to convert the electrical measurements (mA) into engineering values (mbar):


𝑃𝑚𝑏𝑎𝑟= (𝑅𝑚𝐴*𝑆)+700


Where:
Pmbar = Pressure in millibar
RmA = Reading in mA
S = sensitivity as from the Compliance Certificate in mA/mbar (usually 25 mbar/mA)

 
FAQ#077 - Quelles sont les longueurs maximales de câble depuis l'instrument jusqu'à l'enregistreur de données?

 

 

 

 

Les longueurs de câble maximales dépendent de plusieurs facteurs, et en premier lieu le mode d'installation et les protections de câble (blindage, terre, etc...). En supposant que les instruments sont installés selon les règles de l'art, les suggestions suivantes devraient être prises en compte pour la longueur maximale de câble:

INSTRUMENTS NUMERIQUES: voir FAQ#073

INSTRUMENTS ANALOGIQUES: voir ces deux documents:

Guide longueur de câble avec multiplexeurs internes
Guide longueur de câble avec multiplexeurs externes

LT-Inclibus
MD-Profile system

 
FAQ#033 - J'ai reçu le rapport d'étalonnage d'un piézomètre. Le Facteur thermique K n'est pas indiqué. Comment puis-je procéder?

Si la valeur n'est pas indiquée dans le rapport d'étalonnage, vous devez utiliser la formule suivante : K = -1 chiffre/°C. Pour chaque degré d'augmentation de température, vous devez diminuer d'une unité.

 

Piézomètre à corde vibrante

 
FAQ#019 - Quelle est la différence entre les filtres HAE (High-Air Entry) et les filtres LAE (Low-Air Entry)?

Les filtres HAE (High Air Entry) sont normalement utilisés pour surveiller la pression interstitielles dans les barrages à noyau en argile et les sols à faible perméabilité saturés. « High air entry » signifie qu'il y a une haute résistance à l'entrée d'air lorsque le filtre est saturé. La tension de surface de l'eau dans chaque pore très fin du filtre empêche l'entrée d'air. Les filtres HAE doivent être saturés avant installation au moyen d'un appareil de saturation.

Les filtres LAE (Low Air Entry) sont souvent utilisés dans les sols moyens et meubles. Ils n'ont pas besoin d'être saturés par un appareil spécial car la porosité du filtre permet l'entrée de l'eau par simple immersion.

Piézomètre à corde vibrante
Piézomètres piézo-résistifs
Piézomètres en titane

 
FAQ#018 - Quel est le type de protection contre les surtensions intégré dans les piézomètres à corde vibrante?

Un parasurtenseur à plasma est câblé en parallèle avec la bobine (qui est utilisée pour exciter la corde). Le courant de choc de décharge nominal par intervalle de 8-20 microsecondes est de 10 KA. Tension d'amorçage au choc à 1 Kv/ µs : 700 V.

Piézomètre à corde vibrante
Piézomètres multi-points
Capteur de pression amovible
Piézomètres à pénétration directe

 
FAQ#016 - Les piézomètres à corde vibrante sont-ils équipés de capteurs de température ou le capteur de température est-il une option ?

Oui, chaque piézomètre à corde vibrante, comme tous les instruments à corde vibrante de Sisgeo, est équipé d'une thermistance NTC intégrée de type YSI 44005 (3000 Ohms à 25°C). La thermistance n'est pas une option pour les instruments à corde vibrante et n'implique donc aucun surcoût.

Piézomètre à corde vibrante
Piézomètres multi-points
Capteur de pression amovible
Piézomètres à pénétration directe