foto assistance sisgeo1150 320

Assestimetri

 
FAQ#116 - How do I configure a WR-Log digital node to read RS485 Sisgeo TIMED sensors?

Sisgeo digital instruments can operate in two powering modes: TIMED or ALWAYS-ON (for more information see F.A.Q.#094 here https://www.sisgeo.com/products/faq/item/which-are-the-available-powering-mode-for-sisgeo-digital-sensors.html ).
A string of mixed instruments consisting of TIMED gauges and ALWAYS-ON gauges cannot work.
The first thing to do is therefore to check that ALL connected instruments in your array are set to TIMED mode.
You can check the powering mode of your gauges in the calibration reports of each instrument as in the example below.
The numbers "3-3" after "TIMED" are the "warming delay" and "address delay" values to be entered in the APP wizard set-up page.

TIMED example

 

In order to correctly set-up the WR-Log app for reading a string of Sisgeo digital gauges in TIMED powering mode, please follow the next screenshot as example:

- choose the protocol "Sisgeo v3" 
- insert the correspondent Warming delay value (in our example 3)
- insert the correspondent Adress delay value (in our example 3)
- insert the addresses of the gauges in your string, separated by comma without any space, in ASCENDING order (do NOT inser the addresses in random order!)
NOTE: in TIMED mode, the reading time is about WARMING_DELAY x HIGHER_RS485_ADDRESS, in our case 3 x 20 = about 60 seconds.
So, if your string is composed by 20 gauges BUT with addresses from 200 to 220, the reading time is about 3 x 220 = 660 seconts (11 minutes) to read the same 20 gauges. So that, is really important to correctly set-up the addresses of the gauges of the string to be read.

Digital node TIMED

Estensimetri DEX ed Estenso-Inclinometri DEX-S
Celle di carico elettriche per tiranti
Inclinometri fissi da foro
Sistema RDS (Railway Deformation System)
Clinometri a barra analogici e digitali
Clinometri o tiltmetri digitali
H-Level - Sistema di monitoraggio cedimenti
Inclinometri fissi BH-Profile
Inclinometri fissi orizzontali
WR LOG wireless dataloggers
LT-Inclibus
MD-Profile system

 
FAQ#111 - Why I cannot read correctly my 4-20mA current loop gauge?

It could be a problem connected to the power supply given by the readout or logger. When the power supply is in the current loop (2-wire gauge) it is necessary to consider the effect of voltage drop across the shunt resistor on the voltage applied to the gauge.

For example, suppose a 4-20mA gauge requires at least 12 V to operate correctly and the readout powered with 16 V. The voltage the gauge sees is the voltage supplied by the readout minus the voltage drop in the rest of the current loop. At 20 mA output, the voltage drop across the commonly used 100 ohm resistor is 2 V.

When the voltage supplied by the readout is 16 V, this leaves 14 V for the gauge and everything is fine.
However, if the readout is powered with less than 14 V, at 20 mA current it will leave less than 12 V for the gauge. In this case, the output of the transmitter may be in error.

Deformometri a filo
Inclinometri fissi da foro
Estensimetro a filo
Assestimetro idraulico multipunto
MPBX - Estensimetro multibase da foro
MEXID Estensimetro multibase miniaturizzato
Estensimetri a punto fisso e a piastra
Celle di carico elettriche per tiranti
Celle di pressione totale per terreno
Celle di carico elettro-idrauliche per centine e puntoni
Fessurimetri elettrici e a corda vibrante
Mini OMNIAlog - datalogger 4 canali
Martinetti piatti
Celle di carico resistive per prove di carico su palo
H-Level - Sistema di monitoraggio cedimenti
Convergence extensometer (DISCONTINUED)
Piezometri Piezo-Resistivi
Trasduttori relativi per livello di falda
Trasduttori removibili per piezometri Casagrande
Piezometri in titanio
Piezometri ad infissione
Clinometri di superficie analogici

 
FAQ#110 - What's the purpose of the linear and polynomial factors written in the Calibration Reports?

Utilize the Linear Sensitivity Factors (A, B) and Ploynomial Sensitivity Factors (A, B, C, D) of the Calibration Reports permit to obtain readings in engineerig units with a maximum error as for the Calibration Report.

In the case of analogue gauges, the factors shall be applied on the electrical readings (i.e. mA, mV, digit, etc...)

In the case of digital gauges in "Legacy mode" (digital gauges with FW version 0.X, 1.X, 2.X or 3.X), the factors shall be applied on the output in engineering units (i.e. sin angle, kPa, etc...)

In the case of digital gauges in "Normal Mode" (digital gauges with FW version 3 or higher), the factors are already applied inside the gauge, so the Sensitivity Factors shall not be utilized with these instruments.
NOTE: all the new digital gauges are in "Normal mode".

For more information regarding SISGEO Calibration Report, refer to the following video https://youtu.be/BF8e3ZRcaYU

For more information on "how to use" the Sensitivity Factors with analogue gauges and with digital gauges in Legacy Mode, refer to the instruments manuals or to the following document: https://www.sisgeo.com/uploads/manuali/Addendum_data_processing/ADDENDUM_-_DATA_PROCESSING_-_EN_00.pdf

 

 

LT-Inclibus
MD-Profile system

 
FAQ#094 - Which are the available powering modes for SISGEO digital sensors?

All SISGEO digital gauges can be settled in two different powering mode:

  • ALWAYS ON: all digital sensors switched on together. Faster solution, but high power consumption. The system will take about 1 second to read each gauge.
  • TIMED: the sensors are powered and switched-on one by one. Reading of the chain take more time than "always on", but the power consumption is lower. In this case the system will take about 3 seconds to read each gauge.

The STANDARD powering mode is ALWAYS ON, so unless otherwise requested by the Customer, the sensors are settled as default in ALWAYS ON.

 

 

 

 

 

Estensimetri DEX ed Estenso-Inclinometri DEX-S
Inclinometri fissi da foro
Clinometri a barra analogici e digitali
Clinometri o tiltmetri digitali
H-Level - Sistema di monitoraggio cedimenti
Inclinometri fissi BH-Profile
LT-Inclibus
MD-Profile system

 
FAQ#087 - Could the IPI, BH Profile and DEX probes have problems in frozen water?

Sisgeo suggest that frozen water within the inclinometer casings is to be avoided due to following reasons:

- Ice within the casing will affect functionality of the systems by blocking the individual probes;
- Mechanical damages can occur to the probes, but also to the inclinometer casing due to the expansion of frozen water

In any case, inclinometers and DEX probes can work until -30°C so that sensors will be not damaged.

What can be done to avoid this?
- insert a heating cable that keeps water temperature above 0°C;
- remove water from the inclinometer casing;
- place the inclinometer/DEX probes at locations where temperatures remain above 0°C.

Inclinometri fissi da foro
Estensimetri DEX ed Estenso-Inclinometri DEX-S
Inclinometri fissi BH-Profile
Inclinometri fissi orizzontali

 
FAQ#081 - Qual è la massima lunghezza del cavo per la sonda DEX e il DEX-S?

La massima lunghezza del cavo strumentale dalla sonda DEX al datalogger è 200m. Se il sistema di acquisizione dati include i multiplexer box esterni (architettura distribuita), la massima lunghezza del cavo è 200m dalla sonda DEX al multiplexer box esterno più altri 200m dal multiplexer box esterno a OMNIAlog (in totale 400m)

Estensimetri DEX ed Estenso-Inclinometri DEX-S

 
FAQ#077 - Which are the maximum cable lengths from instrument to datalogger?

The cable lengths depend from many factors, first of all installation and cable protections (screen, earth, etc...). Assuming that instruments are installed in a workmanlike, for the maximum cable lengths should be followed the next suggestions:

DIGITAL INSTRUMENTS: see FAQ#073

ANALOGUE INSTRUMENTS: see both documents:

Cable length guide line with internal multiplexers
Cable length guide line with external multiplexers

 

 

 

 

LT-Inclibus
MD-Profile system

 
FAQ#073 - Qual è il numero massimo di sensori digitalizzati (RS-485, modbus), il numero massimo di catene e la distanza massima del cavo di collegamento in una rete RS-485?

Ultimo aggiornamento: ottobre 2021

Tutti i sensori digitalizzati SISGEO utilizzano il una interfaccia RS485 con protocollo Modbus.

  1. Il numero massimo di sensori digitalizzati in una rete RS-485 è 247 (teorico).
  2. Il numero massimo di catene di sensori digitalizzati collegabili ad un Modbus master (OMNIAlog e miniOMNIAlog) è 4.
  3. Per le distanze massime e il numero massimo di sensori, si faccia riferimento alle tabelle qui di seguito:

Always ON Digital gauges

TIMED digital instruments

NOTA: la somma delle lunghezze dei cavi delle colonne "A" e "C" non deve essere superiore a 1000m. Le prescrizioni nelle colonne A e B evitano problemi di caduta eccessiva della tensione di alimentazione lungo la linea RS-485 garantendo così il corretto funzionamento.

 

 

Sistema RDS (Railway Deformation System)
OMNIAlog Datalogger
Sistema inclinometrico digitale (FUORI PRODUZIONE)
Inclinometri fissi da foro
Clinometri a barra analogici e digitali
Clinometri o tiltmetri digitali
Mini OMNIAlog - datalogger 4 canali
H-Level - Sistema di monitoraggio cedimenti
Inclinometri fissi BH-Profile
Inclinometri fissi orizzontali
LT-Inclibus
MD-Profile system

 
FAQ#035 - In what consists a profiler? Which is its function?

The profiler consists of:

  • a stainless steel measurement sensor for pressure measures;
  • a cable reel containing the liquid tank;
  • an electro-hydraulic cable for signals transmission;
  • a tripod on which the reel/tank should be positioned.

The electro-hydraulic cable follows the probe (measuring sensor) to which it is connected. A small steel cable to pull the profiler probe is also provided; it should be situated into the same HDPE tube where the probe pass through (readings with two operators with both sides of HDPE tube accessible) or in a second tube located parallel to the first one (readings with one operator or one not-accessible side; in this last case a pulley system is recommended).

Finally, what you need to execute readings with the profiler is only a probe in HDPE with diameter ≥ 50 mm. We suggest you the HDPE and not a metallic tube because this kind of tube (without crash-it) must be adapted to the embankment differential settlements. It is advised to use a HDPE tube with diameter which is not more than 50mm to avoid mistakes or less accuracy in readings.

 
FAQ#031 - Is the DEX system suitable for in-place applications?

DEX system has been designed for automatic soil settlement monitoring (vertical movement) in unattended location. DEX system consists of a string of DEX probes installed in borehole within a ABS inclinometer casing. DEX-S, the combined inclinometer-settlement probe, provides both horizontal movements (X, Y-axis) and vertical settlement (Z-axis) for 3-D borehole automatic profile monitoring.

Estensimetri DEX ed Estenso-Inclinometri DEX-S

 
FAQ#012 - How is important the function of the grout to the operation of the spider magnets?

The arms of the spider only keep the magnet in place while grouting, but the grout couples the magnet to the surroundig soil. Grout mix shall be controlled (ratio water/cement) during grouting operation according to the soil application.

Assestimetro magnetico di tipo BRS

 
FAQ#011 - Are the air bubbles present in the liquid mix cause of errors?

Sisgeo liquid mix is de-aired at factory and it is supplied sealed in special tank. However in the DSM reference gauge there is a high sensitive sensor which is able to monitor the weight of the liquid within the reservoir. In the case of the air bubbles come over decreasing the level of the liquid in the reservoir the sensor measures this change. Thus air bubbles are not usually a problem.

Assestimetro idraulico multipunto
H-Level - Sistema di monitoraggio cedimenti